Firemain (UK) Limited
Call 0208 523 1919

Panels

 

AOV Single Zone

Product Image Technical
Input Voltage 240v AC 50Hz (+5%/-5%)
Output Voltage 24v DC (+10%/ -10%)
Output Rating AOV-001 : 1Amp
  AOV-003 : 3Amp
  AOV-005 : 5Amp
  AOV-007 : 10Amp
Charge Current AOV-001 : 0.25Amp
  AOV-003 : 0.5Amp
  AOV-005 : 1Amp
  AOV-007 : 1.5Amp
Product Details      
Enclosure Size 400mmW x 300mH x 110mmD Input Options Manual Override Keyswitch
Weight AOV-001 : 7.0kgs   Break Glass
  AOV-003 : 7.6kgs   Smoke Detector
  AOV-005 : 7.6kgs   Temperature Sensor
  AOV-007 : 9.0kgs   Rain Sensor
Battery Type Sealed Lead Acid Output Options Electrically Operated Chain Actuators
Enclosure Colour RAL 7035    
Description

Our Automatic Opening Vent Control Unit is designed to control 24vdc electric window actuators and may be used with any other equipment which requires reverse voltage to close.

The AOV Control Unit has been designed to interface with any conventional or addresable Fire Alarm Panel and other Building Management Systems.

In addition the AOV Control Unit may be used with single or multiple smoke detectors and/or break glass units as a standalone product.

Real time fault monitoring is used to indicate mains fail, charge fail and output ail. The onboard fault relay can also be used to provide volt free contact to signal any faults to a remote monitoring system, remote indicator or a small buzzer unit making the unit an integral part of any addressable system.

The system can also be set up to work from rain or temperature sensors. In the event of outside weather or indoor temperature changes the AOV panel can be triggered to open or close windows or vents when required.

Modular design means that the unit can be supplied in one, three and five amp models in a single self contained interface and Control unit.

A special design service is also available to manufacture an AOV unit to any customer specification.

 

AOV Multi Zone

Product Image Technical
Input Voltage 240v AC 50Hz (+5%/-5%)
Output Voltage 24v DC (+10%/ -10%)
Output Rating AOV5/A: 5Amp
  AOV10/A or /B: 10Amp
  AOV20/B : 20Amp
  AOV15/C : 15Amp
  AOV30/C : 30Amp
Charge Current AOV5/A : 1Amp
  AOV10/A or /B: 1.5Amp
  AOV20/B : 3Amp
  AOV15/C : 3Amp
  AOV30/C : 4.5Amp
   
Product Details      
Enclosure Size /A : 400mmW x 400mH x 160mmD Input Options Manual Override Keyswitch
  /B : 700mmW x 500mH x 200mmD   Break Glass
  /C : 900mmW x 500mH x 200mmD   Smoke Detector
Weight     Temperature Sensor
      Rain Sensor
Zone output Each zone used requires an AOVZ-01 Output Options Electrically Operated Chain Actuators
  zone card. Battery Type Sealed Lead Acid
    Enclosure Colour RAL 9010
Description

Our Automatic Opening Vent Control Unit is designed to control 24vdc electric window actuators and may be used with any other equipment which requires reverse voltage to close. For example the Multi zone system can be used for natural or smoke ventilation controlling vents, valves & windows.

The unit has been designed to interface with any conventional or addresable Fire Alarm Panel and other Building Management Systems.

In addition the AOV Control Unit may be used with single or multiple smoke detectors and/or break glass units as a standalone product.

A master zone can be set up which will trigger together with any other zone. A roof vent (shaft or stairwell) can open together with a window. This will then vent smoke from the vent & also from the original window (or zone) triggered.

The panel can also be set to trigger from temperature or rain sensors. This means the system can control natural ventilation where high & low temperatures will be set.

Real time fault monitoring is used to indicate mains fail, charge fail and output fail. The onboard fault relay can also be used to provide volt free contact to signal any faults to a remote monitoring system, remote indicator or a small buzzer unit making the unit an integral part of any addressable system.

Modular design means that the unit can be supplied in one, three and five amp models in a single self contained interface and Control unit.

A special design service is also available to manufacture an AOV unit to any customer specification.